Shelf life of a dry charge battery is five years plus. Store in a cool dry area. The positive plate has an unlimited shelf life. The negative plate will revert to lead oxide when in the presence of water and oxygen. If this should happen, the battery is not ruined, but activation will take considerably longer!
The electrolyte temperature will rise dramatically during activation. Do not place on charge until the temperature drops below 115° F. Activation may take several days!
Before installing the batteries, clean the contact surfaces of the lead terminal post and battery terminals with a wire brush. Apply a thin coat of Vaseline to all contact points and connector bolts. After all connections have been securely tightened, they should be gone over and tightened a second time.
The state of charge of a battery can be measured with a hydrometer. The chart below shows the approximate "percent of charge" corrected for temperature at various specific gravity values.
| Charged | Specific Gravity | Open Circuit Voltage |
| 100% | 1.265-1.275 | 12.6 |
| 75% | 1.225-1.235 | 12.4 |
| 50% | 1.190-1.200 | 12.2 |
| 25% | 1.155-1.165 | 12.0 |
| 0% | 1.120-1.130 | 11.7 |
Determining state of charge by voltage is more difficult as there must be no load or surface voltage present.
When taking specific gravity measurements, it is important to correct for temperature to get a true reading. As a rule of thumb, specific gravity will change by 0.003 for each ten degrees Fahrenheit change in temperature above or below 77° F (25° C). Below 77° F subtract from readings and above 77° F add to the readings. As an example a reading of 1.250 at 67° F corrected for temperature would be 1.247 and a reading of 1.250 at 87° F corrected for temperature would be 1.253.
It is recommended that fully charged gravity and voltage readings be taken of each cell every month and compared with readings from the preceding period. The readings will indicate any marked difference in battery condition as well as differences between cells. A good rule of thumb is if there is 0.025 points or less between the high and low cell the battery is not defective. Low readings would indicate the battery being discharged.
The charging system can have a profound effect on the life of the battery. A high voltage setting can cause excessive gassing and water loss. Eventual damage to the battery system will take place. A low setting will leave the batteries in an under charged condition resulting in a loss of capacity and eventually the battery system may not take a charge. A proper setting will result in a minimum of water consumption and still able to maintain the batteries at full charge.