Skip to main content

FLOODED DEEP CYCLE BATTERY

12 HHG 185P

Series 4000 Warranty 3 Years
Volts 12 Design 4D MOD
Cells 6 Plates/Cell 17
Terminal Type Flag
Included Hardware S/S Hex Cap Screw, Nut, Lock & Flat Washer
Size & Thread 5/16"-18
Charge
Charge Voltage Range 14.7-15 V/cell @ 25°C (77°F)
Self-Discharge Rate 5%-10% per month at 25°C (77°F)
Capacity
Cold Crank Amps (CCA) 0°F / -18°C 713
Marine Crank Amps (MCA) 32°F / 0°C 891
Reserve Capacity (RC @ 25A) 444 Minutes
Reserve Capacity (RC @ 75A) 148 Minutes
Hour Rate Capacity / AMP Hour Current / AMPs
@ 100 Hour Rate 246 AH 2.46 A
@ 72 Hour Rate 233 AH 3.24 A
@ 50 Hour Rate 220 AH 4.4 A
@ 20 Hour Rate 185 AH 9.25 A
@ 15 Hour Rate 176 AH 11.72 A
@ 10 Hour Rate 163 AH 16.28 A
@ 8 Hour Rate 159 AH 19.89 A
@ 5 Hour Rate 146 AH 29.23 A
@ 1 Hour Rate 74 AH 74 A

Ampere hour capacity ratings based on specific gravity of 1.280 at 27°C (80°F).
Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250.

Specifications
Weight 55 kg 121.5 lbs
Length 527 mm 20.75"
Width 222 mm 8.75"
Height Incl. Term. 254 mm 10"
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components.
Electrolyte Reserve 57 mm 2.25"
Container (Inner) Polypropylene
Cover (Inner) Polypropylene - heat sealed to inner container
Container (Outer) High Density Polyethylene
Cover (Outer) High Density Polyethylene snap fit to outer container
Handles Molded
  • Plastics are UL94 HB (UL94-V2 available)
  • Plastics are impact copolymer rated to ASTM D256, D5420
  • Vented design with integral flame arrestor vent caps

Cycle Life vs. Depth of Discharge

Rev.#4 | August 2024